Images are representations only.

Vegator 142 Signal Conditioning

Brand: VEGA
The VEGATOR 142 is a signal conditioning instrument for level detection for sensors with Analog measured data transmission such as typically capacitive electrodes, hydroStatic-Pressure transmitters or process pressure transmitters. 

Simple monitoring and control functions can be realized. 

Typical applications are two-point control, pump control (On/Off) and monitoring functions such as overfill and dry run protection.
Features
  • Compact Separator with Alarm Function for Limit Level
  • Comprehensive Monitoring Detects Short circuit and Measuring Line Break as well as Malfunctions in the Sensor
  • Simple Mounting Through Carrier Rail as well as Detachable, Coded Terminals
The VEGATOR 142 is a signal conditioning instrument for level detection for sensors with Analog measured data transmission such as typically capacitive electrodes, hydroStatic-Pressure transmitters or process pressure transmitters. 

Simple monitoring and control functions can be realized. 

Typical applications are two-point control, pump control (On/Off) and monitoring functions such as overfill and dry run protection.
Features
  • Compact Separator with Alarm Function for Limit Level
  • Comprehensive Monitoring Detects Short circuit and Measuring Line Break as well as Malfunctions in the Sensor
  • Simple Mounting Through Carrier Rail as well as Detachable, Coded Terminals

Specifications

Brand

Ambient Temperature Range

  • -20° to 60° C (-4° to 140° F)

Approvals & Certifications

  • ATEX
  • GOST
  • IEC
  • SIL 2

Consumption

  • 3 W (8 VA)

Display

  • LED Display

Electrical Connectors

  • 0.25 mm² (AWG 23) to 2.5 mm² (AWG 12) - Wire Cross Section
  • EN 50022 / 60715
  • Screw Terminal

Environmental Protection

  • IP20

Hysteresis

  • 100 µA

Operating Voltages

  • 24-230 Vac
  • 24-65 Vdc
  • 50/60 Hz

Relay Output

  • Adjustable Delay - 2/6/8 seconds, ± 20 %
  • Basic Delay - 150 milliseconds, ± 10 %
  • Breaking Capacity: 50 mW Min., 500 VA, 54 W DC, Max.
  • Quantity: 2 x Operating Relay
  • Switching Current: 10 µA Min., 3 A AC, 1 A DC, Max.
  • Switching Voltage: 10 mVdc Min., 250 Vac, 60 Vdc, Max.

Sensor Input

  • Active - Input Sensor Supply through VEGATOR 142
  • Current Limitation: 23 mA through Internal Resistance 100 ohms, ± 1 % - Passive Input
  • Current Limitation: 23 mA through Internal Resistance 200 ohms, ± 1 % - Active Input
  • Detection: ≤ 3.6 mA (Line Break), ≥ 21 mA (Short Circuit)
  • Number of Sensors: 2 x 4-20 mA
  • Passive Input: Sensor Has an Own Power Supply

Switch Type

  • SPDT

Terminal Voltage

  • 18.2 Vdc, ± 5 %

Transmission Value

  • 4-20 mA