Approvals & Certifications
- ATEX
- CE
- CRN
- CRN - Alberta
- CRN - British Columbia
- CRN - Manitoba
- CRN - N.W. Territories
- CRN - Saskatchewan
- CSA
- cUL
- Dual Seal
- EMC
- LVD
- PED
- RoHS
- RTN
- UL
Deadband, Approximate - Bottom of Range
- -13° to -7° C (9° to 19° F)
- 5° to 11° C (41° to 52° F)
Deadband, Approximate - Top of Range
- -16° to -14° C (3° to 6° F)
- 2° to 8° C (36° to 46° F)
Electrical - Free Leads
- 18” (45 cm) Free Leads
- 18” (45 cm) Teflon Leadwire
Electrical Certification
- ATEX - Baseefa Certified for Potentially Explosive Atmospheres. Models 646**Y, II 2 GD Ex d IIC, Ex Tb IIIC, Baseefa 05-ATEX-0011X. (Option Y)
- c-UL, UL/CSA Explosion-proof: Div. 1, 2 Hermetically Sealed Electrical Assembly P/N 17-51 (17-73 for M Model Option), Listed by Both Underwriter’s Laboratories, Inc. (File No. E32961) & Canadian Standard Association (CSA)Testing Laboratories (File No. L
Electrical Rating
- 1 A at 125 Vac, 50/60 Hz
- 15 A at 125/250/480 Vac Resistive, 0.5 A at 125 DC, 0.2 A at 250 DC
- 5 A at 125/250 Vac Resistive, 5 A at 28 DC, 0.5 A at 125 DC
Environmental Protection
- IP54
- IP66
- NEMA 13
- NEMA 4, 7, 9, 13 / IP54, 66
- NEMA 7
- NEMA 9
Maximum Sensor, Probe Temperature
- 121° to 260° C (250° to 500° F)
Operating Temperature
- -40° to 86° C (-40° to 187° F)
Proof Pressure
- bar: 103.4
- kPa: 10,342
- psig: 1,500
Sensor, Probe Material
- Stainless Steel with Nickel-Plated Steel
Set Point - Decreasing
- -39° to 212° C
- -39° to 212° C (-38° to 414° F)
Set Point - Increasing
- -34° to 216° C
- -34° to 216° C (-30° to 420° F)
System Pressure
- bar: 86
- kPa: 8,618
- psig: 1,250