Vegator 111 Signal Conditioning

Brand: VEGA
The VEGATOR 111 is a signal conditioning instrument for point level detection with the vibrating level switches VEGASWING, VEGAVIB and VEGAWAVE with electronics version according to NAMUR (IEC 60947- 5-6). 

Simple control functions can be realized with this combination. 

Typical applications are monitoring functions such as overflow or dry run protection. 

A fault signal output is available as an option.
Features
  • Comprehensive monitoring detects short circuit and measuring line break as well as malfunctions in the sensor
  • Simple and convenient line monitoring via test key (also for SIL and WHG)
  • Simple mounting through carrier rail as well as detachable, coded terminals
The VEGATOR 111 is a signal conditioning instrument for point level detection with the vibrating level switches VEGASWING, VEGAVIB and VEGAWAVE with electronics version according to NAMUR (IEC 60947- 5-6). 

Simple control functions can be realized with this combination. 

Typical applications are monitoring functions such as overflow or dry run protection. 

A fault signal output is available as an option.
Features
  • Comprehensive monitoring detects short circuit and measuring line break as well as malfunctions in the sensor
  • Simple and convenient line monitoring via test key (also for SIL and WHG)
  • Simple mounting through carrier rail as well as detachable, coded terminals

Specifications

Brand

Ambient Temperature Range

  • -20° to 60° C (-4° to 140° F)

Approvals & Certifications

  • ATEX
  • GOST
  • IEC
  • SIL 2

Consumption

  • 2 W (8 VA)

Display

  • LED Display

Electrical Connectors

  • 0.25 mm² (AWG 23) to 2.5 mm² (AWG 12) - Wire Cross-Section
  • EN 50022 / 60715
  • Screw Terminal

Environmental Protection

  • IP20

Input

  • NAMUR

Operating Voltages

  • 24-230 Vac
  • 24-65 Vdc
  • 50/60 Hz

Relay Output

  • Basic Switch-On / Switch-Off Delay: 100 milliseconds
  • Breaking Capacity: 50 mW Min., 500 VA, 54 W DC, Max.
  • Quantity: 1 x Operating Relay, 1 x Fail-safe Relay
  • Switching Current: 10 µA DC Min., 3 A AC, 1 A DC, Max.
  • Switching Voltage: 10 mVdc Min., 250 Vac, 60 Vdc, Max.

Sensor Input

  • ± 100 µA - Switching Threshold Tolarance
  • 1.5 mA - Switching Threshold On
  • 1.7 mA - Switching Threshold Off
  • Active (Sensor Power Supply by VEGATOR)
  • Current Limitation: through Internal Resistance (1 kiloohms, ± 1 %)
  • Detection: ≤ 0.05 mA (Line Break), ≥ 6.8 mA (Shortcircuit)
  • Terminal Voltage: 8.2 V Dc, ± 5 %
  • Transmission - 1.2 to 2.1 mA Analog

Switch Type

  • SPDT - Contact