Series 662 Programmable HART® Dual Input Field Temperature Transmitter

Brand: Pyromation
The Series 662 programmable dual input HART® field temperature transmitter is a 2-wire unit with analog output.

It includes input for RTDs; resistance inputs in 2-wire, 3-wire, and 4-wire connections; thermocouples and voltage signals.

The transmitter can be supplied with or without a digital display, in either a general-purpose aluminum housing, or explosion-proof aluminum housing. 

The Series 662 can be programmed with a PC or a HART® protocol handheld terminal. When supplied with a digital display, the LCD screen shows the current measured value and a bar graph with limit value violation indicator.
Features
  • Universally programmable with HART® protocol for various input signals
  • lluminated display, rotatable
  • Operation, visualization and maintenance with PC
  • 2-wire technology, analog output (4 to 20) mA
  • Highly accurate in entire operating temperature range
  • Approvals: FM and CSA (IS, NI, XP and DIP)
  • Galvanic isolation, 2kV (Sensor input to the output)
  • Output simulation
  • Min./max. process values recorded
  • Customized measuring range setup or expanded Setup
The Series 662 programmable dual input HART® field temperature transmitter is a 2-wire unit with analog output.

It includes input for RTDs; resistance inputs in 2-wire, 3-wire, and 4-wire connections; thermocouples and voltage signals.

The transmitter can be supplied with or without a digital display, in either a general-purpose aluminum housing, or explosion-proof aluminum housing. 

The Series 662 can be programmed with a PC or a HART® protocol handheld terminal. When supplied with a digital display, the LCD screen shows the current measured value and a bar graph with limit value violation indicator.
Features
  • Universally programmable with HART® protocol for various input signals
  • lluminated display, rotatable
  • Operation, visualization and maintenance with PC
  • 2-wire technology, analog output (4 to 20) mA
  • Highly accurate in entire operating temperature range
  • Approvals: FM and CSA (IS, NI, XP and DIP)
  • Galvanic isolation, 2kV (Sensor input to the output)
  • Output simulation
  • Min./max. process values recorded
  • Customized measuring range setup or expanded Setup

Specifications

Output Signal

  • Analog (4 to 20) mA or (20 to 4) mA

Transmission as

  • Temperature Linear
  • Resistance Linear
  • Voltage Linear

Induced Current Required

  • ≤ 3.5 mA

Current Limit

  • ≤ 23 mA

Response Time

  • 1 s

Sensor Breakage / Short Circuit

  • Un-Configured - ≤ 3.6 mA or ≥ 21.0 mA
  • Configured - 21.6 mA to 23 mA

Cable Entry

  • Three 1/2” NPT Openings