Description
The VEGATOR 141 is a signal conditioning instrument for level detection for sensors with Analog measured data transmission such as typically capacitive electrodes, hydroStatic-Pressure transmitters or process pressure transmitters.
Simple monitoring and control functions can be realized.
Typical applications are pump control (On/Off) and monitoring functions such as overfill and dry run protection.
Features- Compact Separator with Alarm Function for Limit Level
- Comprehensive Monitoring Detects Short circuit and Measuring Line Break as Well as Malfunctions In the Sensor
- Simple Mounting Through Carrier Rail as Well as Detachable, Coded Terminals
Configure
Specifications
Specifications
Brand
Ambient Temperature Range
- -20° to 60° C (-4° to 140° F)
Approvals & Certifications
- ATEX
- GOST
- IEC
- SIL 2
Consumption
- 2 W (8 VA)
Display
- LED Display
Electrical Connectors
- 0.25 mm² (AWG 23) to 2.5 mm² (AWG 12) - Wire Cross Section
- EN 50022 / 60715
- Screw Terminal
Environmental Protection
- IP20
Hysteresis
- 100 µA - Switching Threshold Hysteresis
Operating Voltages
- 24-230 Vac
- 24-65 Vdc
- 50/60 Hz
Relay Output
- Breaking Capacity: 50 mW Min., 500 VA, 54 W DC, Max.
- Quantity 1 x Operating Relay, 1 x Fail-safe Relay - Optional
- Switching Current: 10 µA Min., 3 A AC, 1 A DC, Max.
- Switching Voltage: 10 mVdc Min., 250 Vac, 60 Vdc, Max.
- Switch-On/Switch-Off Delay - 2/6/8 seconds, ± 20 % - Adjustable Delay
- Switch-On / Switch-Off Delay: 150 milliseconds, ± 10 % - Basic Delay
Sensor Input
- Active Input: Sensor Supply through VEGATOR 141
- Current Limitation: through Internal Resistance 23 mA(100 ohms, ± 1 %) - Passive Input
- Current Limitation: through Internal Resistance 23 mA(200 ohms, ± 1 %) - Active Input
- Detection: ≤ 3.6 mA (Line Break), ≥ 21 mA (Short Circuit)
- Number of Sensors: 1 x 4-20 mA
- Passive Input: Sensor Has an Own Power Supply
Switch Type
- SPDT Contact - Floating
Terminal Voltage
- 18.2 Vdc, ± 5 % - Idle State
Transmission Value
- 4-20 mA - Analog Sensors